The room sensors are used to provide reliable, accurate temperature readings in surface-mount room environments, Energy Management Control Systems, compatible with all the leading control systems.They feature a standard plastic ventilated enclosure.
Product Highlights:
Three low cost room temperature sensors to choose from.
High precision thermistor or RTD, accurate to 0.2C(+/-.36F).
This sensor is used to measure the outside air temperature to allow the DDC system to coordinate the mechanical systems with actual building load conditions, enabling such strategies as free cooling, optimum start/stop, and supply temperature reset. The housing is made from PVC and stainless steel fittings which shield the probe from direct sunlight. There are three thermistor based models, and one RTD version to provide compatibility with the majority of DDC systems.
This sensor is used to measure the supply and return temperature in HVAC system. The flange mount design makes it easy to install the sensor in tight quarters. There are several sensor elements to choose from which guarantee compatibility with all popular DDC systems. The probe in the photo is our standard model which is always in stock, it has a 8″ probe and a 120″ cable, and employs either a precision thermistor or platinum film sensor, so field calibration is not required. The 10ft(3m) cable is “Plenum Rated”.
The temperature sensor is designed to measure outdoor air temperature in typical HVAC applications. Mounting is quick and easy using two screws and no electrical box. The thermistor is a well sealed stainless steel probe which is then inserted into a hard rubber PVC radiation shield. The cable is two meters long which allows terminating inside the building in an electrical enclosure or with flying leads. The cable can exit directly behind the probe and into the building through a hole, or it can exit vertically and run down the wall. A foam backing seals the hole in the wall if there is one and also serves to thermally insulate the probe from the wall. The probe is filled with thermal grease for quick response.
The tamper proof room temperature sensor with Torx security screws designed for use with building automation systems in commercial buildings, hospitals, museums or other facilities requiring accurate measurement of room temperature. This sensor can be directly mounted to drywall or an 11-10 electrical handy box.
This sensor is used to measure water temperature of heated or chilled water and other liquids found in the various mechanical systems of building. The sensor is especially intended for strapping to the outside of a pipe when there is no opportunity to install a well such as in a retrofit or additions to an existing system.The strap on probe is useful in applications such as monitoring batteries, transformers, generators, and generally any place where a complete assembly can not be mounted,Ice rink slabs and soil temperature are other applications.
This sensor is used to measure water temperature of heated or chilled water and other liquids in mechanical systems. The sensor is called an immersion type where the sensor is mounted in a brass or stainless steel thermowell which allows the probe to be removed from the pipe without draining the system and protects the probe.There are four thermistor based models, and one RTD version to provide compatibility with the majority of DDC systems.
The sensor measures temperature in stratified air such as the mixing sections of air handlers. The sensor has a standard 10k type 2 temperature-resistance curve compatible with all major control systems.